2013-02-11 15:26:05 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: |
| |
| 1. NOT CLEAR WHICH PRODUCT IS PROPOSED. NOA 12-0209.06 |
| SUBMITTED, INSTALLATION SCHEDULE REFERS TO NOA |
| 12-0209.07. THE FOLLOWING REVIEW COMMENTS ARE BASED ON |
| THE NOA SUBMITTED, 12-0209.06. |
| |
| 2. SEE COLUMN: SHUTTER MOUNTING CONNECTION TYPE PER |
| PRODUCT APPROVAL. THIS SHOULD CORRELATE WITH THE ANCHOR |
| DETAILS ON SHEET 12 (FOR WOOD STRUCTURES). |
| |
| 4TH REVIEW, STATES LAG SCREWS. THIS IS THE FASTENER. |
| PROVIDE CONNECTION TYPE PROPOSED; ALTERNATIVE 1 THROUGH |
| ALTERNATIVE 8. PLEASE NOTE THAT 6" FASTENING APPEARS TO |
| COMPLY FOR ALL CONNECTION TYPES BUT LAG SCREWS NOT THE |
| CORRECT FASTENER FOR ALL CONNECTION TYPES. |
| |
| 3. OK. |
| |
| 4. IF NOA 12-0209.07 IS PROPOSED, PLEASE PROVIDE TWO |
| SETS OF PRODUCT APPROVALS. IF NOA 12-0209.07 IS |
| PROPOSED, REVISE INSTALLATION SCHEDULE AND RESUBMIT. |
| |
| NOT ADDRESSED. PLEASE CLARIFY WHICH PRODUCT IS TO BE |
| INSTALLED. NOA #12-0209.06 SUBMITTED, BUT INSTALLATION |
| SCHEDULE PROPOSES 12-0209.07. |
| |
| NEW COMMENT: |
| |
| PREVIOUS INSTALLATION SCHEDULES HAD FOUR OPENINGS, THIS |
| ONE HAS TWO. PLEASE INCLUDE ALL OPENINGS OR OTHERWISE |
| PROVIDE IMPACT PROTECTION FOR OPENINGS 1 AND 4 WHICH |
| WERE NOT INCLUDED ON THE LATEST INSTALLATION SCHEDULE. |
| |