2013-02-11 15:26:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. NOT CLEAR WHICH PRODUCT IS PROPOSED. NOA 12-0209.06
 SUBMITTED, INSTALLATION SCHEDULE REFERS TO NOA
 12-0209.07. THE FOLLOWING REVIEW COMMENTS ARE BASED ON
 THE NOA SUBMITTED, 12-0209.06.
  
 2. SEE COLUMN: SHUTTER MOUNTING CONNECTION TYPE PER
 PRODUCT APPROVAL. THIS SHOULD CORRELATE WITH THE ANCHOR
 DETAILS ON SHEET 12 (FOR WOOD STRUCTURES).
  
 4TH REVIEW, STATES LAG SCREWS. THIS IS THE FASTENER.
 PROVIDE CONNECTION TYPE PROPOSED; ALTERNATIVE 1 THROUGH
 ALTERNATIVE 8. PLEASE NOTE THAT 6" FASTENING APPEARS TO
 COMPLY FOR ALL CONNECTION TYPES BUT LAG SCREWS NOT THE
 CORRECT FASTENER FOR ALL CONNECTION TYPES.
  
 3. OK.
  
 4. IF NOA 12-0209.07 IS PROPOSED, PLEASE PROVIDE TWO
 SETS OF PRODUCT APPROVALS. IF NOA 12-0209.07 IS
 PROPOSED, REVISE INSTALLATION SCHEDULE AND RESUBMIT.
  
 NOT ADDRESSED. PLEASE CLARIFY WHICH PRODUCT IS TO BE
 INSTALLED. NOA #12-0209.06 SUBMITTED, BUT INSTALLATION
 SCHEDULE PROPOSES 12-0209.07.
  
 NEW COMMENT:
  
 PREVIOUS INSTALLATION SCHEDULES HAD FOUR OPENINGS, THIS
 ONE HAS TWO. PLEASE INCLUDE ALL OPENINGS OR OTHERWISE
 PROVIDE IMPACT PROTECTION FOR OPENINGS 1 AND 4 WHICH
 WERE NOT INCLUDED ON THE LATEST INSTALLATION SCHEDULE.
  