2013-01-23 15:23:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. NOT CLEAR WHICH PRODUCT IS PROPOSED. NOA 12-0209.06
 SUBMITTED, INSTALLATION SCHEDULE REFERS TO NOA
 12-0209.07. THE FOLLOWING REVIEW COMMENTS ARE BASED ON
 THE NOA SUBMITTED, 12-0209.06.
  
 2. SEE COLUMN: SHUTTER MOUNTING CONNECTION TYPE PER
 PRODUCT APPROVAL. THIS SHOULD CORRELATE WITH THE ANCHOR
 DETAILS ON SHEET 12 (FOR WOOD STRUCTURES).
  
 3. ANCHOR SPACING DOES NOT COMPLY WITH THE MAJORITY OF
 THE ANCHOR SPACING ON SHEET 12.
  
 4. IF NOA 12-0209.07 IS PROPOSED, PLEASE PROVIDE TWO
 SETS OF PRODUCT APPROVALS. IF NOA 12-0209.07 IS
 PROPOSED, REVISE INSTALLATION SCHEDULE AND RESUBMIT.
  
 REVIEW FOR 12-0209.07 AND INSTALLATION SCHEDULE
 SUBMITTED HAS NOT BEEN DONE AS PRODUCT PROPOSED IS NOT
 CLEAR.
  
  