2013-01-22 17:28:21****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. DESIGN INTENT NOT CLEAR; ENGINEER SPECIFIES +-65.4
 AS REQUIRED MINIMUM DESIGN PRESSURE, AND ALSO STATES ON
 SHEET 1 DOOR'S DP LIMITATIN IS +-65 (OTHER OPTIONS
 AVAILABLE IN PRODUCT APPROVAL). SEE FBC 1609. EITHER
 SUBMIT A COMPLIANT DOOR, REVISE THE DOOR DP
 REQUIREMENT, OR PLEASE CONTACT ME TO DISCUSS.
  
  
  