Plan Review Notes For Permit 12110195 |
Permit Number |
12110195 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-01-22 17:28:21 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. DESIGN INTENT NOT CLEAR; ENGINEER SPECIFIES +-65.4 | | AS REQUIRED MINIMUM DESIGN PRESSURE, AND ALSO STATES ON | | SHEET 1 DOOR'S DP LIMITATIN IS +-65 (OTHER OPTIONS | | AVAILABLE IN PRODUCT APPROVAL). SEE FBC 1609. EITHER | | SUBMIT A COMPLIANT DOOR, REVISE THE DOOR DP | | REQUIREMENT, OR PLEASE CONTACT ME TO DISCUSS. | | | | | | |
|