Plan Review Notes For Permit 12110195 |
Permit Number |
12110195 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-19 14:57:25 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS, | | FBC 106. A PLAN WAS PROVIDED BY SHOWS X'S ON A ROOF, NO | | WALLS, NOT CLEAR WHERE DOORS WILL BE INSTALLED. | | | | 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | FS471. | | | | 3. THE PRODUCT APPROVAL SUBMITTED FL 15454 HAS A DESIGN | | PRESSURE LIMITATION OF +-60. THIS DOES NOT MEET | | MINIMUMS SPECIFIED BY ENGINEER. HAVE THE ENGINEER | | REVIEW ALL PRODUCT APPROVALS PRIOR TO RESUBMITTAL FBC | | 1609, FBC 107.3.4.1. | | | | 4. PLEASE INDICATE WHICH DOORS ARE FIRE RATED, SPECIFY | | FIRE RATING AND RATING OF STAIR OR STORAGE WALL, AS | | WELL AS INFORMATION ABOUT WHAT IS CONTAINED IN THE | | STORAGE AREAS, FBC CHAPTER 7. | | | | |
|