Plan Review Notes
Plan Review Notes For Permit 12110195
Permit Number 12110195
Review Stop B
Sequence Number 1
Notes
Date Text
2012-11-19 14:57:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS,
 FBC 106. A PLAN WAS PROVIDED BY SHOWS X'S ON A ROOF, NO
 WALLS, NOT CLEAR WHERE DOORS WILL BE INSTALLED.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 3. THE PRODUCT APPROVAL SUBMITTED FL 15454 HAS A DESIGN
 PRESSURE LIMITATION OF +-60. THIS DOES NOT MEET
 MINIMUMS SPECIFIED BY ENGINEER. HAVE THE ENGINEER
 REVIEW ALL PRODUCT APPROVALS PRIOR TO RESUBMITTAL FBC
 1609, FBC 107.3.4.1.
  
 4. PLEASE INDICATE WHICH DOORS ARE FIRE RATED, SPECIFY
 FIRE RATING AND RATING OF STAIR OR STORAGE WALL, AS
 WELL AS INFORMATION ABOUT WHAT IS CONTAINED IN THE
 STORAGE AREAS, FBC CHAPTER 7.
  
  