2012-11-13 14:57:252010 FBC
  
 REVISION IS DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO.
 08-0221.04 HAS BEEN SUPERSEDED BY NOA NO.08-0922.04.
 PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL. DCA RULE
 9N-3
  
 2) THE ENGINEERING SPECIFIES AN ALLOWABLE UPLIFT
 PRESSURE OF -457.5 PSF FOR THE APPROVED ASSEMBLY THAT
 WILL BE INSTALLED. THE ASSEMBLY WITH THIS MAXIMUM
 DESIGN PRESSURE IS FOR NON-INSULATED CONCRETE DECKS.
 HOWEVER, THE APPROVED ASSEMBLY THAT WAS SUBMITTED (PAGE
 8 OF 27) IS FOR AND INSULATED CONCRETE DECK WITH A
 MAXIMUM DESIGN PRESSURE OF -140 PSF. PLEASE CORRECT.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW