2012-12-17 09:13:25FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 THERE IS NOT ENOUGH INFORMATION INCLUDED FOR A PLUMBING
 REVIEW.
 AN OCCUPANCY TYPE (CHURCH ?), AND OCCUPANT LOAD WILL BE
 REQUIRED TO DETERMINT THE REQUIRED PLUMBING FIXTURES.
 FBC PLUMBING 403.1 REQUIRED PLUMBING FIXTURES FOR
 CHURCH:
 WATER CLOSETS FOR MEN = 1 PER 150
 WATER CLOSETS FOR WOMEN = 1 PER 150
 LAVATORIES = 1 PER 200
 DRINKING FOUNTAINS = 1 PER 1000 * (HI/LO TYPE REQUIRED
 PER FBC ACCESSIBILITY 211.2).
 SERVICE SINK = 1
  