Plan Review Notes For Permit 12110149 |
Permit Number |
12110149 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-04 12:20:03 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | THERE IS NOT ENOUGH INFORMATION INCLUDED FOR A PLUMBING | | REVIEW. | | AN OCCUPANCY TYPE (CHURCH ?), AND OCCUPANT LOAD WILL BE | | REQUIRED TO DETERMINT THE REQUIRED PLUMBING FIXTURES. | | FBC PLUMBING 403.1 REQUIRED PLUMBING FIXTURES FOR | | CHURCH: | | WATER CLOSETS FOR MEN = 1 PER 150 | | WATER CLOSETS FOR WOMEN = 1 PER 150 | | LAVATORIES = 1 PER 200 | | DRINKING FOUNTAINS = 1 PER 1000 * (HI/LO TYPE REQUIRED | | PER FBC ACCESSIBILITY 211.2). | | SERVICE SINK = 1 | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|