Plan Review Notes
Plan Review Notes For Permit 12110067
Permit Number 12110067
Review Stop B
Sequence Number 2
Notes
Date Text
2013-02-26 14:04:01****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2ND REVIEW - ANCHOR SPACING WAS LEFT BLANK. PLEASE
 COMPLETE.
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3. FOR THE WINDOWS, PROVIDE A FLOOR PLAN SHOWING:
 WINDOW LOCATIONS, SIZES, WINDOW TYPE, ROOM
 DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW)
 AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1.
 THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 HORIZONTAL ROLLER WINDOWS PROPOSED FOR A 36X72 WINDOW.
 SEE PRODUCT APPROVAL, 63" IS THE MAX ALLOWED FOR THIS
 WINDOW. A 36" WIDE HORZONTAL ROLLER WINDOW WOULD NOT
 MEET EMERGENCY EGRESS REQUIREMENTS. NOT ENOUGH
 INFORMATION PROVIDED TO DETERMINE CODE COMPLIANCE.
  
 4. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 NOT ADDRESSED. OUR RECORDS SHOW THAT THERE ARE OTHER
 SHUTTERS INSTALLED ON THIS STRUCTURE. PLEASE INCLUDE
 EMERGENCY MEANS OF ESCAPE ON THE FLOOR PLAN.
  
 NEW COMMENT:
  
 5. TWO SETS OF ALL DOCUMENTS REQUIRED FOR PERMIT
 ISSUANCE FBC 107.
  