2012-11-13 13:25:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. DESIGN INTENT IS NOT CLEAR. THE PLAN STATES THAT
 SHUTTERS WILL BE INSTALLED, SHUTTER PRODUCT APPROVAL
 SUBMITTED, BUT THE WINDOW PRODUCT APPROVAL SUBMITTED IS
 FOR AN IMPACT GLASS PRODUCT.
  
 IF SHUTTERS ARE PROPOSED, ADDRESS THE FOLLOWING
 COMMENTS. IF SHUTTERS ARE NOT PROPOSED, PLEASE REVISE
 PLAN.
  
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
  