2012-12-28 18:07:12 | ***PROVISO*** |
| ***REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S |
| DISCRETION*** |
| |
| |
| UNDER FLOOR VENTILATION SHALL BE PROVIDED AS FOLLOWS: |
| |
| R408.1 VENTILATION. |
| THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR |
| JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE |
| OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS |
| THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM |
| NET AREA OF VENTILATION OPENINGS SHALL NOT BE LESS THAN |
| 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 SQUARE FEET (14 |
| M2) OF UNDER-FLOOR SPACE AREA, UNLESS THE GROUND |
| SURFACE IS COVERED BY A CLASS 1 VAPOR RETARDER |
| MATERIAL. WHEN A CLASS 1 VAPOR RETARDER MATERIAL IS |
| USED, THE MINIMUM NET AREA OF VENTILATION OPENINGS |
| SHALL NOT BE LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR |
| EACH 1,500 SQUARE FEET (140 M2) OF UNDER-FLOOR SPACE |
| AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3 |
| FEET (914 MM) OF EACH CORNER OF THE BUILDING. |
| |
| EXCEPTION: CRAWL SPACES, DESIGNED BY A FLORIDA LICENSED |
| ENGINEER OR REGISTERED ARCHITECT TO ELIMINATE THE |
| VENTING. |
| |
| R408.2 OPENINGS FOR UNDER-FLOOR VENTILATION. |
| THE MINIMUM NET AREA OF VENTILATION OPENINGS SHALL NOT |
| BE LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 |
| SQUARE FEET (14 M2) OF UNDER-FLOOR AREA. ONE |
| VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF |
| EACH CORNER OF THE BUILDING. VENTILATION OPENINGS SHALL |
| BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF THE |
| FOLLOWING MATERIALS PROVIDED THAT THE LEAST DIMENSION |
| OF THE COVERING SHALL NOT EXCEED 1/4 INCH (6.4 MM): |
| |
| |
| 1. PERFORATED SHEET METAL PLATES NOT LESS THAN 0.070 |
| INCH (1.8 MM) THICK. |
| 2. EXPANDED SHEET METAL PLATES NOT LESS THAN 0.047 INCH |
| (1.2 MM) THICK. |
| 3. CAST-IRON GRILL OR GRATING. |
| 4. EXTRUDED LOAD-BEARING BRICK VENTS. |
| 5. HARDWARE CLOTH OF 0.035 INCH (0.89 MM) WIRE OR |
| HEAVIER. |
| 6. CORROSION-RESISTANT WIRE MESH, WITH THE LEAST |
| DIMENSION BEING 1/8 INCH (3.2 MM) THICK. |
| |
| EXCEPTION: THE TOTAL AREA OF VENTILATION OPENINGS SHALL |
| BE PERMITTED TO BE REDUCED TO 1/1,500 OF THE |
| UNDER-FLOOR AREA WHERE THE GROUND SURFACE IS COVERED |
| WITH AN APPROVED CLASS I VAPOR RETARDER MATERIAL AND |
| THE REQUIRED OPENINGS ARE PLACED TO PROVIDE CROSS |
| VENTILATION OF THE SPACE. THE INSTALLATION OF OPERABLE |
| LOUVERS SHALL NOT BE PROHIBITED. |
| |
| 2. ACCESS TO UNDER FLOOR SPACE |
| |
| R408.4 ACCESS. |
| ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES. |
| ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF |
| 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS |
| THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16 |
| INCHES BY 24 INCHES (407 MM BY 610 MM). WHEN ANY |
| PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN |
| AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM BY |
| 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY |
| SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING. |
| THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER |
| A DOOR TO THE RESIDENCE. SEE SECTION M1305.1.4 FOR |
| ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| LOCATED UNDER FLOORS |
| |
| |
| |
| |
| |
| |
| |
| |