Plan Review Notes For Permit 12100962
Permit Number 12100962
Review Stop B
Sequence Number 1
Notes
Date Text
2012-12-28 18:07:12***PROVISO***
 ***REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S
 DISCRETION***
  
  
 UNDER FLOOR VENTILATION SHALL BE PROVIDED AS FOLLOWS:
  
 R408.1 VENTILATION.
 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS
 THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM
 NET AREA OF VENTILATION OPENINGS SHALL NOT BE LESS THAN
 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 SQUARE FEET (14
 M2) OF UNDER-FLOOR SPACE AREA, UNLESS THE GROUND
 SURFACE IS COVERED BY A CLASS 1 VAPOR RETARDER
 MATERIAL. WHEN A CLASS 1 VAPOR RETARDER MATERIAL IS
 USED, THE MINIMUM NET AREA OF VENTILATION OPENINGS
 SHALL NOT BE LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR
 EACH 1,500 SQUARE FEET (140 M2) OF UNDER-FLOOR SPACE
 AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3
 FEET (914 MM) OF EACH CORNER OF THE BUILDING.
  
 EXCEPTION: CRAWL SPACES, DESIGNED BY A FLORIDA LICENSED
 ENGINEER OR REGISTERED ARCHITECT TO ELIMINATE THE
 VENTING.
  
 R408.2 OPENINGS FOR UNDER-FLOOR VENTILATION.
 THE MINIMUM NET AREA OF VENTILATION OPENINGS SHALL NOT
 BE LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR EACH 150
 SQUARE FEET (14 M2) OF UNDER-FLOOR AREA. ONE
 VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF
 EACH CORNER OF THE BUILDING. VENTILATION OPENINGS SHALL
 BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF THE
 FOLLOWING MATERIALS PROVIDED THAT THE LEAST DIMENSION
 OF THE COVERING SHALL NOT EXCEED 1/4 INCH (6.4 MM):
  
  
 1. PERFORATED SHEET METAL PLATES NOT LESS THAN 0.070
 INCH (1.8 MM) THICK.
 2. EXPANDED SHEET METAL PLATES NOT LESS THAN 0.047 INCH
 (1.2 MM) THICK.
 3. CAST-IRON GRILL OR GRATING.
 4. EXTRUDED LOAD-BEARING BRICK VENTS.
 5. HARDWARE CLOTH OF 0.035 INCH (0.89 MM) WIRE OR
 HEAVIER.
 6. CORROSION-RESISTANT WIRE MESH, WITH THE LEAST
 DIMENSION BEING 1/8 INCH (3.2 MM) THICK.
  
 EXCEPTION: THE TOTAL AREA OF VENTILATION OPENINGS SHALL
 BE PERMITTED TO BE REDUCED TO 1/1,500 OF THE
 UNDER-FLOOR AREA WHERE THE GROUND SURFACE IS COVERED
 WITH AN APPROVED CLASS I VAPOR RETARDER MATERIAL AND
 THE REQUIRED OPENINGS ARE PLACED TO PROVIDE CROSS
 VENTILATION OF THE SPACE. THE INSTALLATION OF OPERABLE
 LOUVERS SHALL NOT BE PROHIBITED.
  
 2. ACCESS TO UNDER FLOOR SPACE
  
 R408.4 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16
 INCHES BY 24 INCHES (407 MM BY 610 MM). WHEN ANY
 PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN
 AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM BY
 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY
 SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING.
 THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER
 A DOOR TO THE RESIDENCE. SEE SECTION M1305.1.4 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED UNDER FLOORS
  
  
  
  
  
  
  
  