2012-11-02 10:26:42RESIDENTIAL (R3) REPAIRS/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- WALL SECTIONS: SHOW HOW ARE THE LOADS TRANSFERED
 FROM CEILING TO FOUNDATION AS REQUIRED BY SEC. R601.2
 OF 2010 FBC-RESIDENTIAL. HOW IS THE WALL ATTACHED TO
 NEW 3 1/2" X 7" PARALLAM BEAM?. WALL SECTIONS SUBMITTED
 DON'T SPECIFY ANY CONNECTORS HERE.
  
 2- SPECIFY HOW ARE ALL THE FLOOR FRAMING MEMBERS
 PROTECTED FROM DECAY AS REQUIRED BY SEC. R317.1.
  
 3- SPECIFY CRAWL SPACE VENTILATION AS REQUIRED BY SEC.
 R408.1.
 NOTE; ALSO CHECK THE ALUMINUM TRAILER SKIRT
 MANUFACTURER' SPECIFICATIONS. THEY REQUIRE VENTILATION.
  
 4- CLARIFY IF REPLACING EXISTING ENTRY DOOR OR
 REBUILDING THE ENTRY DOOR FRAMING TO VERIFY COMPLIANCE
 WITH SEC. 601.2 OF 2010 FBC-EXISTING BUILDING. SPECIFY
 SIZE OF EXISTING DOOR. REBUILDING THE DOOR FRAME
 REQUIRES COMPLIANCE WITH SEC. 602.4 OF 2010
 FBC-EXISTING BUILDING. SEE SEC. R311.2 OF 2010
 FBC-RESIDENTIAL FOR REQUIRED SIZE.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS: ACCORDING TO THE MIAMI-DADE
 WEBSITE NOA 09-0316.10 SUBMITTED WAS SUPERSEDED. VISIT
 THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
 RESUBMIT CURRENT NOA. PRODUCT APPROVALS REQUIRED BY DCA
 RULE 9N-3.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ARCHITECT ON PLANS SUBMITTED. PROVIDE ONLY THE COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 6- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  