Date |
Text |
2012-11-02 10:26:42 | RESIDENTIAL (R3) REPAIRS/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- WALL SECTIONS: SHOW HOW ARE THE LOADS TRANSFERED |
| FROM CEILING TO FOUNDATION AS REQUIRED BY SEC. R601.2 |
| OF 2010 FBC-RESIDENTIAL. HOW IS THE WALL ATTACHED TO |
| NEW 3 1/2" X 7" PARALLAM BEAM?. WALL SECTIONS SUBMITTED |
| DON'T SPECIFY ANY CONNECTORS HERE. |
| |
| 2- SPECIFY HOW ARE ALL THE FLOOR FRAMING MEMBERS |
| PROTECTED FROM DECAY AS REQUIRED BY SEC. R317.1. |
| |
| 3- SPECIFY CRAWL SPACE VENTILATION AS REQUIRED BY SEC. |
| R408.1. |
| NOTE; ALSO CHECK THE ALUMINUM TRAILER SKIRT |
| MANUFACTURER' SPECIFICATIONS. THEY REQUIRE VENTILATION. |
| |
| 4- CLARIFY IF REPLACING EXISTING ENTRY DOOR OR |
| REBUILDING THE ENTRY DOOR FRAMING TO VERIFY COMPLIANCE |
| WITH SEC. 601.2 OF 2010 FBC-EXISTING BUILDING. SPECIFY |
| SIZE OF EXISTING DOOR. REBUILDING THE DOOR FRAME |
| REQUIRES COMPLIANCE WITH SEC. 602.4 OF 2010 |
| FBC-EXISTING BUILDING. SEE SEC. R311.2 OF 2010 |
| FBC-RESIDENTIAL FOR REQUIRED SIZE. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) SINGLE HUNG WINDOWS: ACCORDING TO THE MIAMI-DADE |
| WEBSITE NOA 09-0316.10 SUBMITTED WAS SUPERSEDED. VISIT |
| THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. |
| RESUBMIT CURRENT NOA. PRODUCT APPROVALS REQUIRED BY DCA |
| RULE 9N-3. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE |
| ARCHITECT ON PLANS SUBMITTED. PROVIDE ONLY THE COVER |
| PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| |
| 6- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |