2012-10-31 10:46:47 | 12100852 | | 721 BISCAYNE DRIVE | | SFD ELECTRICAL REMODEL | | | | THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN. | | | | PROVISO: | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS. | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|