2012-11-05 12:46:57FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. AN ISOMETRIC DIAGRAM IS REQUIRED FOR THE PLUMBING.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING: 13. PLUMBING RISER
  
 ***NOTE***
 THE SINK RIM IS REQUIRED TO BE 34" AFF MAX.
 FBC 2010 ACCESSIBILITY CODE 2010 606.3 HEIGHT:
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  