Plan Review Notes For Permit 12100654 |
Permit Number |
12100654 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-05 12:46:57 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. AN ISOMETRIC DIAGRAM IS REQUIRED FOR THE PLUMBING. | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | 107.3.5.1.3 PLUMBING: 13. PLUMBING RISER | | | | ***NOTE*** | | THE SINK RIM IS REQUIRED TO BE 34" AFF MAX. | | FBC 2010 ACCESSIBILITY CODE 2010 606.3 HEIGHT: | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|