Plan Review Notes
Plan Review Notes For Permit 12100654
Permit Number 12100654
Review Stop B
Sequence Number 1
Notes
Date Text
2012-11-13 11:17:50BUILDING PLAN REVIEW
 PERMIT: 12100654
 ADD: 400 W RAILROAD AVE. 4TH FLOOR
 CONT: TBD
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 13/ 2012
 ACTION: DENIED
  
 1) PLANS FAIL TO PROVIDE LOCATION OF SUITE, THEY
 INDICATE THE 4TH FLOOR, THERE ARE OTHER PROJECTS ALSO
 LOCATED ON THE FOURTH FLOOR, BE SUITE SPECIFIC. 2010
 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE LOCATION...
  
 2) PLEASE PROVIDE ADDITIONAL INFORMATION (CLARITY) AS
 TO THE FRONT ENTRY DOOR, THE DEMOLISION PLAN DOES NOT
 APPEAR TO HAVE ANY WORK TO BE COMPLETED ON THE ENTRY
 DOOR, THE LIFE SAFETY PLAN IT APPEARS TTHE ENTRY DOOR
 IS BEING MOVED AND REHUNG AS TO THE SWING OF THE DOOR
 WHEREAS ON SHEET A100 IT APPEARS TO BE IN THE SAME
 LOCATION AND THESWING OF THE DOOR APPEARS TO REMAIN THE
 SAME. 107.2.1.
  
 3) SHEET A100 THE RECEPT ROOM DOOR # 2 IS MISSING THE
 REQUIRED 18" ON THE LATCH SIDE OF THE DOOR. 2010
 FLORIDA ACCESSIBILITY CODE FIGURE 404.2.4.1 (A).
  
 4) A100 GALLEY # 105 INDICATES A KITCHEN SINK, THERE IS
 NO CUT SECTION THROUGH THIS AREA PROVIDING COMPLIANCE
 WITH 2010 ACCESSIBILTY CODE 606.3 HEIGHT REQUIREMENT OF
 34" TO THE RIM OR COUNTER FROM FINISH FLOOR.
  
 5) A100 IN BOTH THE WATING ROOM (101) AND OFFICE (103)
 BOTH INDICATE GLAZING IN THE WALL WITHIN 24" OF THE
 DOOR PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 2406.4(6) HAZARDOUS LOCATION.
  
 6) A100 PLANS DO NOT PROVIDE ANY EMERGENCY LIGHTING IN
 ACCORDANCE WITH 2010 FBC-B 1006.2 NOR ANY EXIT SIGNAGE
 OR DIRECTIONALS1006.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy