Plan Review Notes
Plan Review Notes For Permit 12100609
Permit Number 12100609
Review Stop E
Sequence Number 1
Notes
Date Text
2012-10-31 10:16:3912100609
 5200 N. FLAGLER DRIVE # 1103
 APARTMENT REMODEL
  
 SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW AND
 EXISTING LIGHTING OUTLETS, RECEPTACLE OUTLETS AND SMOKE
 DETECTORS. NEC 215.5
 VERIFY SMOKE ALARMS ARE PROVIDED INSIDE AND OUTSIDE ALL
 SLEEPING AREAS. 2010 FBC R314, 315
 VERIFY THE KITCHEN COUNTER TOP RECEPTACLES AND BATHROOM
 RECEPTACLES ARE GFCI PROTECTED. NEC 210.8
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
  