2012-10-30 15:52:46 | BUILDING PLAN REVIEW |
| PERMIT: 12100606 |
| ADD: 5200 N FLAGLER # 2302 |
| CONT: A & A DEVELOPMENT |
| TEL: (561)719-0895 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| BUILDING PROVISO: |
| |
| IF FLOOR TILE ARE TO BE INSTALLED COMPLIANCE WITH THESE |
| SECTIONS WILL NEED TO BE SUBMITTED TO THE BUILDING |
| DEPARTMENT: |
| |
| 1) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2) 2010 FBC-B 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| CONSTRUCTION |
| 603.1 ALLOWABLE MATERIALS (1). INSULATION PLACED |
| BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT |
| AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 100. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |