Plan Review Notes
Plan Review Notes For Permit 12100583
Permit Number 12100583
Review Stop E
Sequence Number 1
Notes
Date Text
2012-11-14 14:42:1712100583
 316 BANYAN BLVD.
 COMMERCIAL REMODEL
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR THE
 ELECTRICAL DISCONNECTS AND FOR FLASH PROTECTION. NEC
 110.22, 110.16
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, ALARM
 SYSTEMS AND SITE LIGHTING.
  
  