2012-11-08 16:35:13 | BUILDING PLAN REVIEW |
| PERMIT: 12100583 |
| ADD: 316 BANYAN BLVD |
| CONT: TBD |
| TEL: (561)###-#### |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| NOV. 08/ 2012 |
| ACTION: DENIED |
| |
| 1) SHEET A0.1& S1.3 WIND DESIGN IS INDICATED AS A |
| EXPOSURE "B". 2010 FBC-B 1609.4.2SURFACE ROUGHNESS |
| CATEGORIES SURFACE ROUGHNESS C. THIS SURFACE ROUGHNESS |
| SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE |
| THAN 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET |
| IN THE UPWIND DIRECTION. |
| THIS WILL RAISE THE PRESSURES ON ALL SUBMITTED PRODUCT |
| APPROVALS. TO BE RE-REVIEWED UNDER C EXPOSURES. |
| |
| 2) ROOFING PRODUCT APPROVAL 09-0506.03 GAF PRODUCT |
| APPROVAL DOES NOT HAVE WHICH SUB-SYSTEM IDENTIFIED. |
| PAGE 6 & 7 BOTH HAVE PRESSURES LOW FOR ZONES 2 &3. THE |
| PRODUCT APPROVAL REFERS TO THE ROOFING APPLICATION |
| STANDARD RAS 117 FOR INSTALATION INSTRUCTIONS. |
| |
| 3) ROOFING PRODUCT APPROVAL 12-0308.19 WILL NEED TO |
| IDENTIFY WHICH INSTALATION METHOD WILL BE USED IN |
| INSTALLING THE SPANISH S NUEVO CONCRETE TILE. |
| |
| 4) SHEET A-1.5 THE ROOFING SHEET INDICATES THERE ARE |
| CONCRETE ROOF TILE HIP & RIDGE CAPS THERE ARE NO |
| DETAILS AS TO ATTACH THE HIP AND RIDGE CAP TILE. 2010 |
| FBC-B 1507.37 & 1507.3.8 TO BE IN ACCORDANCE WITH FRSA/ |
| TRI 07320. |
| |
| 5) SHEET A-1.5 INDICATES THE ROOF TOP HATCH IS LOCATED |
| WITHIN 10 FEET OF THE ROOF, MUST COMPLY WITH 2010 FBC-B |
| 1013.6 ROOF ACCESS. |
| |
| 6) NO PRODUCT APPROVAL HAS BEEN SUBMITTED FOR THE DRIVE |
| THROUGH WINDOW, MUST MEET THE REQUIREMENTS FOR 2010 |
| FBC-B 1609.1.2 OPENING PROTECTION, 1609.4.4.1COMPONENTS |
| & CLADDING & RULE 9N3 (31) (B) WINDOWS. |
| |
| 7) SHEET A-4.7 DETAIL 4 ROOF DRAINS, PLEASE PROVIDE A |
| ROOF INSULATION LAYOUT SHEET SHEET A1.5 APPEARS TO HAVE |
| TAPERED INSULATION. THE ENERGY CALCULATIONS |
| INDICATE THE INSULATION TO BE A R VALUE OF R19.8 PLEASE |
| PROVIDE LAYOUT SHEET WITH THE R19.8 VALUE AT THE ROOF |
| DRAINS AND FROM THAT POINT TAPERING UP. BOAF REPORT |
| 5438 A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, A |
| MINIMUM, NOT AN AVERAGE. |
| |
| 8) SHEET A3.2 SECTION #1 THROUGH THE BUILDING PROVIDES |
| THE R19.8 INSULATION ON TOP OF THE ROOF DECK BUT THE |
| SLOPED ROOF TILE SECTION DOES NOT INDICATE WHERE THE |
| ROOF INSULATION WILL BE PLACED? 2010 FBC ENERGY |
| 502.3.5.1 VENTED VERSES UNVENTED? |
| |
| 9) WHEN THE ADDRESS OF 316 BANYAN BLVD IS TYPED INTO |
| OUR GIS ONLY LOT # 5 THE TWO STORY LOT APPEARS, A UNITY |
| OF TITLE WILL BE REQUIRED TO UNIFY ALL LOTS INTO A |
| SINGLE LOT SO THE BUILDING WILL BE LOCATED ON ONE LOT. |
| UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| SEE WEBSITE FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| |
| ********************************************* |
| |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION.\ |
| PLEASE BE AWARE WHEN THE BUILDING IS PARTIALLY |
| DEMOLISHED CONTACT P B COUNTY TO SEE IF TAX CREDITS CAN |
| BE TAKEN FOR A SMALLER FOOTPRINT, |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |