2012-11-08 16:35:13BUILDING PLAN REVIEW
 PERMIT: 12100583
 ADD: 316 BANYAN BLVD
 CONT: TBD
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 08/ 2012
 ACTION: DENIED
  
 1) SHEET A0.1& S1.3 WIND DESIGN IS INDICATED AS A
 EXPOSURE "B". 2010 FBC-B 1609.4.2SURFACE ROUGHNESS
 CATEGORIES SURFACE ROUGHNESS C. THIS SURFACE ROUGHNESS
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE
 ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF
 SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE
 THAN 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET
 IN THE UPWIND DIRECTION.
 THIS WILL RAISE THE PRESSURES ON ALL SUBMITTED PRODUCT
 APPROVALS. TO BE RE-REVIEWED UNDER C EXPOSURES.
  
 2) ROOFING PRODUCT APPROVAL 09-0506.03 GAF PRODUCT
 APPROVAL DOES NOT HAVE WHICH SUB-SYSTEM IDENTIFIED.
 PAGE 6 & 7 BOTH HAVE PRESSURES LOW FOR ZONES 2 &3. THE
 PRODUCT APPROVAL REFERS TO THE ROOFING APPLICATION
 STANDARD RAS 117 FOR INSTALATION INSTRUCTIONS.
  
 3) ROOFING PRODUCT APPROVAL 12-0308.19 WILL NEED TO
 IDENTIFY WHICH INSTALATION METHOD WILL BE USED IN
 INSTALLING THE SPANISH S NUEVO CONCRETE TILE.
  
 4) SHEET A-1.5 THE ROOFING SHEET INDICATES THERE ARE
 CONCRETE ROOF TILE HIP & RIDGE CAPS THERE ARE NO
 DETAILS AS TO ATTACH THE HIP AND RIDGE CAP TILE. 2010
 FBC-B 1507.37 & 1507.3.8 TO BE IN ACCORDANCE WITH FRSA/
 TRI 07320.
  
 5) SHEET A-1.5 INDICATES THE ROOF TOP HATCH IS LOCATED
 WITHIN 10 FEET OF THE ROOF, MUST COMPLY WITH 2010 FBC-B
 1013.6 ROOF ACCESS.
  
 6) NO PRODUCT APPROVAL HAS BEEN SUBMITTED FOR THE DRIVE
 THROUGH WINDOW, MUST MEET THE REQUIREMENTS FOR 2010
 FBC-B 1609.1.2 OPENING PROTECTION, 1609.4.4.1COMPONENTS
 & CLADDING & RULE 9N3 (31) (B) WINDOWS.
  
 7) SHEET A-4.7 DETAIL 4 ROOF DRAINS, PLEASE PROVIDE A
 ROOF INSULATION LAYOUT SHEET SHEET A1.5 APPEARS TO HAVE
 TAPERED INSULATION. THE ENERGY CALCULATIONS
 INDICATE THE INSULATION TO BE A R VALUE OF R19.8 PLEASE
 PROVIDE LAYOUT SHEET WITH THE R19.8 VALUE AT THE ROOF
 DRAINS AND FROM THAT POINT TAPERING UP. BOAF REPORT
 5438 A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, A
 MINIMUM, NOT AN AVERAGE.
  
 8) SHEET A3.2 SECTION #1 THROUGH THE BUILDING PROVIDES
 THE R19.8 INSULATION ON TOP OF THE ROOF DECK BUT THE
 SLOPED ROOF TILE SECTION DOES NOT INDICATE WHERE THE
 ROOF INSULATION WILL BE PLACED? 2010 FBC ENERGY
 502.3.5.1 VENTED VERSES UNVENTED?
  
 9) WHEN THE ADDRESS OF 316 BANYAN BLVD IS TYPED INTO
 OUR GIS ONLY LOT # 5 THE TWO STORY LOT APPEARS, A UNITY
 OF TITLE WILL BE REQUIRED TO UNIFY ALL LOTS INTO A
 SINGLE LOT SO THE BUILDING WILL BE LOCATED ON ONE LOT.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.\
 PLEASE BE AWARE WHEN THE BUILDING IS PARTIALLY
 DEMOLISHED CONTACT P B COUNTY TO SEE IF TAX CREDITS CAN
 BE TAKEN FOR A SMALLER FOOTPRINT,
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved