2012-11-20 15:45:56 | RESIDENTIAL (R3) GARAGE CONVERSION/ALTERATION BUILDING |
| REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N. |
| JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES |
| ARE DUE. REQ'D BY COUNTY IMPACT FEE ORDINANCE OF THE |
| UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- THIS IS NOT AN ALTERATION LEVEL 2. THIS IS A CHANGE |
| OF OCCUPANCY AND ALTERATION LEVEL 3. SEE SEC. 406 AND |
| SEC. 912.1.1 OF 2010 FBC-EXISTING BUILDING. REVISE |
| INFORMATION ON COVER SHEET. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) FRENCH DOORS AS SHOWN ON PLANS. NOA 11-1013.22 |
| SUBMITTED EXPIRED ON OCTOBER 18, 2012. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| |
| C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE |
| SPECIFIED CONNECTOR. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY |
| AMENDMENTS TO FBC. |
| ***NOTE: PERSON WHO SIGNED PRODUCT APPROVALS SUBMITTED |
| IS NOT THE ENGINEER OF RECORD. NEED THE SIGNATURE OF |
| THE ENGINEER OF RECORD. |
| |
| 5- ENGINEER OF RECORD TO UPDATE THE FIRM'S "FOREST HILL |
| ENGINEERING, INC." STATUS. ACCORDING TO THE FLORIDA |
| DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION |
| (DBPR) WEBSITE THE STATUS OF THIS FIRM IS NOT CURRENT. |
| ENGINEER TO CONTACT DBPR AND UPDATE ENGINEERING FIRM'S |
| STATUS AS REQUIRED. BY SEC. 61G15-23.002 OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| 6- ENGINEER OF RECORD TO SIGN AND SEAL ALL SHEETS. THE |
| FIRST THREE PAGES WERE NOT SIGNED AND SEALED AS |
| REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| 7- SHEET 3.0: |
| A) WINDOW #4 SHOWN ON THE WINDOW SCHEDULE DOESN'T MATCH |
| WINDOW SHOWN ON FLOOR PLAN AND EXTERIOR ELEVATIONS. |
| REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| B) WINDOWS #3 AND #4 SHOWN ON THE WINDOW SCHEDULE ARE |
| LOCATED ON ZONE 5 NOT 4. REVISE AS REQUIRED. ZONE 5 IS |
| A LEAST 4'-0" SEE NOTE A ON FIGURE R301.2(7) OF 2010 |
| FBC-RESIDENTIAL. |
| |
| C) PROVIDE STRUCTURAL BUCK DETAIL USING 2X BUCK AS |
| SPECIFIED ON WINDOW SCHEDULE NOTE. SPECIFY ALL |
| FASTENERS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) WHERE IS WINDOW #5 SHOWN ON THE WINDOW SCHEDULE. |
| PLANS AND ELEVATIONS DON'T SHOW THIS WINDOW. AND, |
| CLARIFY WHAT KIND OF WINDOW IS "(2)SH-32 PICTURE" AS |
| SPECIFIED ON WINDOW #5. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 8- WIND LOAD SCHEDULE ON SHEET 7.0: |
| A) CLARIFY WHY THE VALUES INDICATED ON THE ROOF WIND |
| AREAS ARE THE SAME FOR ALL THREE ROOF ZONES. SEE TABLE |
| R301.2(2) OF 2010 FBC-RESIDENTIAL. |
| |
| B) CORNER DISTANCE "A" SHALL BE 4'-0" MIN. NOT 3'-0". |
| SEE FIGURE R301.2(7) AND REVISE AS REQUIRED. |
| |
| C) CLARIFY WHY USING 50 S.F. AS THE AREA OF COMPONENT. |
| SEE NOTE A ON THE TABLE R301.2(2) AND REVISE AS |
| REQUIRED. |
| |
| 9-SPECIFY HOW PROVIDING THE REQUIRED HEATING BY SEC. |
| R303.8 OF 2010 FBC-RESIDENTIAL. |
| ***NOTE: THERE ARE NO PLANS SUBMITTED SHOWING ANY A/C |
| WORK. ELECTRICAL PLAN SHOWS A/C UNIT BUT THERE ARE NO |
| PLANS. MECHANICAL PERMIT REQUIRED ALSO. |
| |
| 10- SPECIFY HOW PROTECTING ALL THE WOOD THAT IS SHOWN |
| ON PLANS AND DETAILS WHEN IN CONTACT WITH CONCRETE OR |
| CONCRETE BLOCK. SEC. R317.1 OF 2010 FBC-RESIDENTIAL. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |