Plan Review Notes For Permit 12100553 |
Permit Number |
12100553 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-09 12:22:09 | 12100553 | | 412 MAYFLOWER ROAD | | REMODEL | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE A REVISED ELECTRIC SERVICE RISER PLAN WITH | | PANELS, MAIN BREAKERS, MAIN DISCONNECTS, WIRE SIZES, | | GROUNDING ETC. SHOW LOCATION OF ALL PANEL BOARDS. NEC | | 215.15 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS. | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREA. NEC 210.70, 230.72 | | A RECEPTACLE IS REQUIRED IN THE LAUNDRY. NEC210.52(F). | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|