Plan Review Notes
Plan Review Notes For Permit 12100553
Permit Number 12100553
Review Stop E
Sequence Number 1
Notes
Date Text
2012-11-09 12:22:0912100553
 412 MAYFLOWER ROAD
 REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A REVISED ELECTRIC SERVICE RISER PLAN WITH
 PANELS, MAIN BREAKERS, MAIN DISCONNECTS, WIRE SIZES,
 GROUNDING ETC. SHOW LOCATION OF ALL PANEL BOARDS. NEC
 215.15
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS.
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.70, 230.72
 A RECEPTACLE IS REQUIRED IN THE LAUNDRY. NEC210.52(F).
  
  