Plan Review Notes For Permit 12100553 |
Permit Number |
12100553 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-29 14:39:07 | 2007 FBC | | | | DENIED BY BUILDING | | | | 1) THIS PERMIT WAS APPLIED FOR UNDER THE 2007 FLORIDA | | BUILDING CODE, THEREFORE, THE REVISIONS TO THESE PLANS | | ARE REQUIRED TO COMPLY WITH THE 2007 FBC. FBCR 301.2.1 | | PLEASE CORRECT THE DESIGN DATA ON SHEET A-1. | | | | 2) ON SHEET A-2 THE WALL INSULATION IS REQUIRED TO BE | | R-13 AND THE FLOOR/CEILING ASSEMBLY IS REQUIRED TO BE | | INSULATED WITH R-13. 2007 FBC ENERGY GLITCH AMENDMENTS | | N1102.B. | | | | 3) THE REVISED PLANS SHOW HABITABLE SPACE ON THE FIRST | | FLOOR WHERE THE APPROVED PLANS HAD STORAGE. THE PLANS | | WILL BE REQUIRED TO BE REVIEWED BY PALM BEACH COUNTY TO | | DETERMINE IF IMPACT FEES ARE DUE BEFORE THIS REVISION | | CAN BE APPROVED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|