2012-10-19 11:56:062275 PALM BEACH LAKES BOULEVARD
 PERMIT #12100549
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A REMOTE ANNUNCIATOR OR VOICE CONTROL PANEL AT
 THE MAIN ENTRANCE.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER/LETTER OR
 COMBINATION TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 INDICATE THE METHOD (PHONE LINES, ETC) FIRE ALARM
 SIGNAL TRANSMISSION.
  