2012-10-12 16:12:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEERED RAS 117 CALCULATIONS FOR THE FLAT
 ROOF DO NOT SPECIFY THE WIND SPEED OR THE EXPOSURE
 CATEGORY USED TO DETERMINE THE REQUIRED DESIGN
 PRESSURES. THE STRUCTURE IS LOCATED ON THE INTERCOASTAL
 WATERWAY WHICH MAKES IT EXPOSURE D. THE WIND SPEED IS
 170 MPH VULT / 134 VASD. THE MEAN ROOF HEIGHT IS GIVEN
 AS 25 FEET. THE PRESSURE SPECIFIED FOR THE ROOF ZONES
 ARE INCORRECT. THEY SHOULD BE -50.4 PSF, -108.4 PSF AND
 -127.3 PSF FOR ROOF ZONES 1, 2 AND 3. FBC R301.2.1.4
  
 2) THE PRODUCT APPROVAL FOR THE POLYGLASS SELF-ADHERED
 ROOF SYSTEM NOA NO. 12-0815.07 HAS A MAXIMUM DESIGN
 PRESSURE OF -112.5 PSF PER PAGE 2 OF 26 OF THE NOA.
 THIS PRODUCT WILL NOT MEET THE REQUIRED UPLIFT FOR ROOF
 ZONE 3. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW