2012-10-12 16:12:49 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE ENGINEERED RAS 117 CALCULATIONS FOR THE FLAT | | ROOF DO NOT SPECIFY THE WIND SPEED OR THE EXPOSURE | | CATEGORY USED TO DETERMINE THE REQUIRED DESIGN | | PRESSURES. THE STRUCTURE IS LOCATED ON THE INTERCOASTAL | | WATERWAY WHICH MAKES IT EXPOSURE D. THE WIND SPEED IS | | 170 MPH VULT / 134 VASD. THE MEAN ROOF HEIGHT IS GIVEN | | AS 25 FEET. THE PRESSURE SPECIFIED FOR THE ROOF ZONES | | ARE INCORRECT. THEY SHOULD BE -50.4 PSF, -108.4 PSF AND | | -127.3 PSF FOR ROOF ZONES 1, 2 AND 3. FBC R301.2.1.4 | | | | 2) THE PRODUCT APPROVAL FOR THE POLYGLASS SELF-ADHERED | | ROOF SYSTEM NOA NO. 12-0815.07 HAS A MAXIMUM DESIGN | | PRESSURE OF -112.5 PSF PER PAGE 2 OF 26 OF THE NOA. | | THIS PRODUCT WILL NOT MEET THE REQUIRED UPLIFT FOR ROOF | | ZONE 3. FBC R301.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|