Plan Review Notes
Plan Review Notes For Permit 12100361
Permit Number 12100361
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-04-02 13:19:46550 SOUTH ROSEMARY AVENUE - SUITE #250
 PERMIT #12100361
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-1.0: THE PLANS INDICATE THE OCCUPANT LOAD IN
 THE IMPROV TO BE 873 PERSONS WITH 50% OF THE OCCUPANTS
 EGRESSING THROUGH THE MAIN ENTRANCE AND 50% OF THE
 OCCUPANTS EGRESSING THROUGH THE 2 REMAINING EXIT
 LOCATIONS (IMPROV/COPPER BLUES). IN LOOKING AT THE
 EXISTING LIFE SAFETY PLAN FOR THE IMPROV, THERE APPEARS
 TO ONLY BE 2 EXITS FOR THE IMPROV OCCUPANTS; (1) THE
 MAIN IMPROV ENTRANCE [AS INDICATED] AND (2) EXIT ACCESS
 THROUGH THE ADJACENT SPACE (COPPER BLUES). THIS CURRENT
 EXIT SCHEME WOULD REQUIRE 50% OF THE IMPROV OCCUPANTS
 TO EGRESS THROUGH COPPER BLUES SPACE. PLEASE MODIFY THE
 LIFE SAFETY PLAN TO SHOW 50% OR 436 IMPROV OCCUPANTS
 EXITING THROUGH THE COPPER BLUES SPACE.
  
 SHEET A-2.1: UNIDENTIFIED DOOR (ADJACENT TO DJ BOOTH)
 NEEDS TO HAVE THE DOOR SWING REVERSED SO THE SWING IS
 IN THE DIRECTION OF EGRESS BECAUSE THE DOOR SERVES MORE
 THAN 50 PERSONS EXITING FROM THE IMPROV. PROVIDE PANIC
 HARDWARE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730