Plan Review Notes For Permit 12100361 |
Permit Number |
12100361 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-04-02 13:19:46 | 550 SOUTH ROSEMARY AVENUE - SUITE #250 | | PERMIT #12100361 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET LS-1.0: THE PLANS INDICATE THE OCCUPANT LOAD IN | | THE IMPROV TO BE 873 PERSONS WITH 50% OF THE OCCUPANTS | | EGRESSING THROUGH THE MAIN ENTRANCE AND 50% OF THE | | OCCUPANTS EGRESSING THROUGH THE 2 REMAINING EXIT | | LOCATIONS (IMPROV/COPPER BLUES). IN LOOKING AT THE | | EXISTING LIFE SAFETY PLAN FOR THE IMPROV, THERE APPEARS | | TO ONLY BE 2 EXITS FOR THE IMPROV OCCUPANTS; (1) THE | | MAIN IMPROV ENTRANCE [AS INDICATED] AND (2) EXIT ACCESS | | THROUGH THE ADJACENT SPACE (COPPER BLUES). THIS CURRENT | | EXIT SCHEME WOULD REQUIRE 50% OF THE IMPROV OCCUPANTS | | TO EGRESS THROUGH COPPER BLUES SPACE. PLEASE MODIFY THE | | LIFE SAFETY PLAN TO SHOW 50% OR 436 IMPROV OCCUPANTS | | EXITING THROUGH THE COPPER BLUES SPACE. | | | | SHEET A-2.1: UNIDENTIFIED DOOR (ADJACENT TO DJ BOOTH) | | NEEDS TO HAVE THE DOOR SWING REVERSED SO THE SWING IS | | IN THE DIRECTION OF EGRESS BECAUSE THE DOOR SERVES MORE | | THAN 50 PERSONS EXITING FROM THE IMPROV. PROVIDE PANIC | | HARDWARE. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|