2013-04-16 13:37:41BUILDING PLAN REVIEW
 PERMIT: 12100361
 ADD: 550 S ROSEMARY SUITE 250
 CONT: TO BE DETERMINED
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISOS:
  
 1) SHEET LS-1.0, A-2.0 & A-2.2 ALL INDICATE AN EXIT
 DOOR COMMON TO THE BOTH COPPER BLUE AND THE IMPROV THAT
 WILL NEED TO BE REVERSED, 2010 FBC-B 1008.1.4.1.1.
 OCCUPANT LOAD IS GREATER THAN 50.
  
 2) SHEET LS-1.0 ALSO INDICATES THE USE OF A CHAIR LIFT
 PLEASE PROVIDE DOCUMENTATIONOF COMPLIANCE WITH 2010
 FBC-408 LIMITED USE / LIMITED APPLICATION ELEVATORS,
 (LULA LIFTS) WILL REQUIRE MANUFACTURERS CUT SHEETS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved