Plan Review Notes
Plan Review Notes For Permit 12100355
Permit Number 12100355
Review Stop B
Sequence Number 3
Notes
Date Text
2012-12-19 10:43:55BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DEC. 19/2012
 ACTION: DENIED
  
 1) SEMI -COMPLIED, SEE COMMENT # 2, NOT REVIEWED BY THE
 DESIGNER OF RECORD. SHEET 1 INDICATES THE FRONT JJALOSE
 WINDOWS ABOVE THE STOREFRONT ARE TO BE REPLACED,
 PRODUCT APPROVALS WERE SUBMITTED FOR WINDOW
 REPLACEMENT.
 2010 FBC-B 1609.1.2 PROTECTION OF WINDOWS. PRODUCT
 APPROVALS SUBMITTED FOR NON-IMPACT GLASS. REQUIRES
 PRODUCT APPROVAL FOR STORM SHUTTERS.
 IS THE STOREFRONT SYSTEM BELOW TTHE EXISTING JALOSIE
 WINDOWS ALSO BEING REPLACED?
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (31)(E) STORM SHUTTERS
  
 2) 3RD REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3)3RD REQUEST. 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) 2ND REQUEST , SEMI-COMPLIED. NEW 8X11 SHEET
 INDICATING THE REMOVAAL OF DOOR FROM THE HALLWAY WIDTH
 INDICATED AS 3'-6" IS NOT SIGNED NOR SEALED, NOR IS THE
 REVISION THAT IS CLOUDED INDICATING THE REVISION DATE.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 FROM 2ND REVIEW. NEW COMMENT- THE HALLWAY THAT LEADS
 FROM TTHE FRONT OF THE PHARMACY TO THE BREAKROOM, IN
 THIS REVISION THE SWING OF THE DOOR HAS CHANGED WHICH
 WILL REQUIRE 18" CLEAR ON THE LATCH SIDE OF THE DOOR,
 PLEASE SEE 2010 ACCESSIBILITY CODE FIGURE 404.2.4.1(A).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]