2012-12-17 16:19:35*** MECHANICAL PLAN CORRECTIONS NEEDED ***
  
 1) WALL MOUNTED CONDENSER STAND NEEDS TO BE ON THE
 PLANS & SITE SPECIFIC, OR SUBMIT AN UP TO DATE PRODUCT
 APPROVAL FOR THE STAND. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9B-72 JAN. 1, 2006. (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 PER-ENGINEERED A/C STANDS.AND 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 2) AS NOTED IN LAST REVIEW 11/1/12 NOTE #3. PROVIDE
 OUTDOOR AIR CAL'S. PER 2010 FBC/M 403.3.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732
  