Plan Review Notes For Permit 12100355 |
Permit Number |
12100355 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-12-17 16:19:35 | *** MECHANICAL PLAN CORRECTIONS NEEDED *** | | | | 1) WALL MOUNTED CONDENSER STAND NEEDS TO BE ON THE | | PLANS & SITE SPECIFIC, OR SUBMIT AN UP TO DATE PRODUCT | | APPROVAL FOR THE STAND. FLORIDA DEPARTMENT OF COMMUNITY | | AFFAIRS RULE 9B-72 JAN. 1, 2006. (31) SUB-CATEGORY OF | | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS & | | PER-ENGINEERED A/C STANDS.AND 2010 FBC 107.3.4.1 | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 2) AS NOTED IN LAST REVIEW 11/1/12 NOTE #3. PROVIDE | | OUTDOOR AIR CAL'S. PER 2010 FBC/M 403.3. | | | | MECHANICAL PLAN REVIEW BY: | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 | | |
|