Plan Review Notes
Plan Review Notes For Permit 12100355
Permit Number 12100355
Review Stop B
Sequence Number 2
Notes
Date Text
2012-12-04 11:31:28BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 04/2012
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE FRONT JJALOSE WINDOWS ABOVE
 THE STOREFRONT ARE TO BE REPLACED, PRODUCT APPROVALS
 WERE SUBMITTED FOR WINDOW REPLACEMENT.
 2010 FBC-B 1609.1.2 PROTECTION OF WINDOWS. PRODUCT
 APPROVALS SUBMITTED FOR NON-IMPACT GLASS. REQUIRES
 PRODUCT APPROVAL FOR STORM SHUTTERS.
 IS THE STOREFRONT SYSTEM BELOW TTHE EXISTING JALOSIE
 WINDOWS ALSO BEING REPLACED?
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (31)(E) STORM SHUTTERS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) NEW COMMENT- THE HALLWAY THAT LEADS FROM TTHE FRONT
 OF THE PHARMACY TO THE BREAKROOM, IN THIS REVISION THE
 SWING OF THE DOOR HAS CHANGED WHICH WILL REQUIRE 18"
 CLEAR ON THE LATCH SIDE OF THE DOOR, PLEASE SEE 2010
 ACCESSIBILITY CODE FIGURE 404.2.4.1(A).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved