Notes |
Date |
Text |
2012-10-18 13:42:59 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | PLEASE SHOW SINKS CONNECTING DOWNSTREAM OF RESTROOM WET | | VENT. | | | | 909.1 HORIZONTAL WET VENT PERMITTED. | | ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL | | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE | | HORIZONTAL WET VENT. | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|