Plan Review Notes For Permit 12100355 |
Permit Number |
12100355 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-01 09:02:50 | PLANS DENIED | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | WALL STAND FOR THE CONDENSER. PER SECTION | | 301.12 WIND RESISTANCE 2010 FBC (M) | | 2) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL. | | 2010 FBC (M) | | 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 | | MINIMUM VENTILATION RATES 2010 FBC (M) | | 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS | | ( FOR FRESH AIR) 2010 FLORIDA ENERGY CODE. | | 5) REFER TO SECTION 503.2.1 CALCULATION OF HEATING & | | COOLING LOADS. 2010 FLORIDA ENERGY CODE. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | |
|