2012-11-07 09:51:08 | 12100295 | | 477 S. ROSEMARY AVENUE # 169 | | NEW BOWLING ALLEY / RECREATION COMPLEX | | | | THE FOLLOWING PROVISO WAS PLACED ON THE ELECTRICAL | | PLAN. | | | | PROVISO: | | | | SAFE WORKING CLEARANCES AND DEDICATED WORKING SPACE IS | | REQUIRED AT ALL ELECTRICAL PANEL BOARDS. NEC 110.26, | | 240.24 | | | | THE BOWLING MACHINES AND THE AV EQUIPMENT MUST BE | | LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY | | (NRTL). NEC 110.3, 600.3 | | | | SAFETY LABELING IS REQUIRED FOR ELECTRICAL DISCONNECTS | | AND FOR FLASH PROTECTION. NEC 110.22, 110.16 | | | | SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND | | FIRE ALARM SYSTEMS. | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | |
|