Plan Review Notes
Plan Review Notes For Permit 12100295
Permit Number 12100295
Review Stop E
Sequence Number 1
Notes
Date Text
2012-10-30 15:32:2312100295
 477 S. ROSEMARY AVENUE # 169
 RECREATION COMPLEX
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
  
 SHEET E1:
 NOTE G23: MULTIWIRE BRANCH CIRCUITS REQUIRE A MEANS
 THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED
 CONDUCTORS. NEC 210.4
  
 SHEET E3:
 PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES
 AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC
 410.36, 314.27
  
 SHEET E6:
 PROVIDE A DETAIL FOR THE CORD STRAIN RELIEF REQUIRED
 FOR THE PINSITTER CORD. NEC 400.10
 INDICATE AND LABEL ON THE PLAN THE METHOD SELECTED TO
 PROVIDE THE REQUIRED SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT THE ELECTRICAL PANEL BOARDS.
 NEC 110.26, 240.24
 VERIFY THE BOWLING MACHINES AND THE AV EQUIPMENT ARE
 LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL). NEC 110.3, 600.3
  
 SHEET E 11:
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 FIRE ALARM SYSTEMS
  
  