2012-12-13 11:53:02REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. DUCT SIZES MISSING IN SEVERAL LOCATIONS ON THE
 PLANS. EXAMPLES: RETURN DUCT SERVING STORAGE ROOM 123
 MECH ROOM 124; RETURN DUCT SERVING SOILED LAUNDRY ROOM
 127. THESE ARE ONLY EXAMPLES. PLEASE CHECK ENTIRE PLAN
 AND PROVIDE ALL MISSING DUCT SIZES. FBC-M 603.1
  
 2. PG M201: UNABLE TO DETERMINE DRYER EXHAUST DUCT
 LENGTH ON PLAN. WHAT IS THE TOTAL DEVELOPED LENGTH OF
 ALL VERTICAL AND HORIZONTAL SECTIONS? DRYER EXHAUST
 DUCT SHALL NOT EXCEED 35 FEET UNLESS DRYER
 MANUFATURER'S INSTALLATION INSTRUCTIONS PROVIDE FOR
 LONGER DUCT INSTALLATION. FBC-M 504.6.
  
 3. PG M202: PLEASE CLARIFY THE AIR BALANCE OVERALL.
 THERE APPEARS TO BE MANY AREAS IN WHICH SUPPLY AND
 RETURN ARE 100% EQUAL. IF 100% OF AIR IS BEING
 RETURNED, HOW IS THERE ENOUGH CAPACITY FOR THE SUPPLY
 TO PROVIDE THE REQUIRED QUANTITIES OF VENTILATION AIR
 FOR EACH HABITABLE SPACE PER FBC-M SECTION 403.
  
 4. SHOW HOW THE CONDITIONED SPACE IS TO BE PRESSURIZED
 WITH RESPECT TO THE OUTDOORS (POST-CONSTRUCTION, NOT
 DURING CONTAMINATION PREVENTION STAGE) PER FBC-EC
 SECTION 503.2.10.6.
  
 5. PG M400: DETAIL #5 SHOWS MIN. 1 INCH SUPPORT STRAPS
 FOR FLEXIBLE DUCTS. FLEXIBLE DUCT SUPPORTS ARE REQUIRED
 TO BE MIN. 1.5 INCHES WIDE PER FBC-M 603.10.3.
  
 6. PG M400: PROVIDE WIND RESISTANT ATTACHMENT DETAIL
 FOR ROOF MOUNTED EQUIPMENT. A NOTE ON THE PLAN CALLING
 FOR CODE COMPLIANT INSTALLATION IS NOT SUFFICIENT.
 PROVIDE SUFFICIENT DETAIL TO ALLOW FOR A REVIEW OF THE
 ATTACHMENT METHOD PER FBC-M 301.12 AND FBC-B 106.1.
  
 7. SHOW HOW FAN SHUT-DOWN BY SMOKE DETECTION IS TO BE
 PROVIDED PER FBC-M 606.1. DETAIL #5 ON PG M600 SHOWS
 DUCT SMOKE DETECTORS ON SUPPLY SIDE AND RETURN SIDE. IS
 THIS CORRECT? ALSO, DETAIL DOES NOT SHOW THE DUCT SMOKE
 DETECTORS INTERLOCKED WITH FIRE ALARM SYSTEM. SHOW
 COMPLIANCE WITH FBC-M 606.4.1.
  