2012-12-13 11:53:02 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| FBC 2010 |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. DUCT SIZES MISSING IN SEVERAL LOCATIONS ON THE |
| PLANS. EXAMPLES: RETURN DUCT SERVING STORAGE ROOM 123 |
| MECH ROOM 124; RETURN DUCT SERVING SOILED LAUNDRY ROOM |
| 127. THESE ARE ONLY EXAMPLES. PLEASE CHECK ENTIRE PLAN |
| AND PROVIDE ALL MISSING DUCT SIZES. FBC-M 603.1 |
| |
| 2. PG M201: UNABLE TO DETERMINE DRYER EXHAUST DUCT |
| LENGTH ON PLAN. WHAT IS THE TOTAL DEVELOPED LENGTH OF |
| ALL VERTICAL AND HORIZONTAL SECTIONS? DRYER EXHAUST |
| DUCT SHALL NOT EXCEED 35 FEET UNLESS DRYER |
| MANUFATURER'S INSTALLATION INSTRUCTIONS PROVIDE FOR |
| LONGER DUCT INSTALLATION. FBC-M 504.6. |
| |
| 3. PG M202: PLEASE CLARIFY THE AIR BALANCE OVERALL. |
| THERE APPEARS TO BE MANY AREAS IN WHICH SUPPLY AND |
| RETURN ARE 100% EQUAL. IF 100% OF AIR IS BEING |
| RETURNED, HOW IS THERE ENOUGH CAPACITY FOR THE SUPPLY |
| TO PROVIDE THE REQUIRED QUANTITIES OF VENTILATION AIR |
| FOR EACH HABITABLE SPACE PER FBC-M SECTION 403. |
| |
| 4. SHOW HOW THE CONDITIONED SPACE IS TO BE PRESSURIZED |
| WITH RESPECT TO THE OUTDOORS (POST-CONSTRUCTION, NOT |
| DURING CONTAMINATION PREVENTION STAGE) PER FBC-EC |
| SECTION 503.2.10.6. |
| |
| 5. PG M400: DETAIL #5 SHOWS MIN. 1 INCH SUPPORT STRAPS |
| FOR FLEXIBLE DUCTS. FLEXIBLE DUCT SUPPORTS ARE REQUIRED |
| TO BE MIN. 1.5 INCHES WIDE PER FBC-M 603.10.3. |
| |
| 6. PG M400: PROVIDE WIND RESISTANT ATTACHMENT DETAIL |
| FOR ROOF MOUNTED EQUIPMENT. A NOTE ON THE PLAN CALLING |
| FOR CODE COMPLIANT INSTALLATION IS NOT SUFFICIENT. |
| PROVIDE SUFFICIENT DETAIL TO ALLOW FOR A REVIEW OF THE |
| ATTACHMENT METHOD PER FBC-M 301.12 AND FBC-B 106.1. |
| |
| 7. SHOW HOW FAN SHUT-DOWN BY SMOKE DETECTION IS TO BE |
| PROVIDED PER FBC-M 606.1. DETAIL #5 ON PG M600 SHOWS |
| DUCT SMOKE DETECTORS ON SUPPLY SIDE AND RETURN SIDE. IS |
| THIS CORRECT? ALSO, DETAIL DOES NOT SHOW THE DUCT SMOKE |
| DETECTORS INTERLOCKED WITH FIRE ALARM SYSTEM. SHOW |
| COMPLIANCE WITH FBC-M 606.4.1. |
| |