Plan Review Notes For Permit 12100269 |
Permit Number |
12100269 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-06 11:15:04 | 12100269 | | 4847 FRED GLADSTONE DRIVE | | RENOVATION | | | | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW | | COMMENTS. | | | | E003 | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22, | | 110.16 | | | | E005: | | ELECTRICAL METALLIC TUBING (EMT) IS NOT AN ACCEPTABLE | | WIRING METHOD AS SHOWN MOUNTED ON THE ROOF EXPOSED TO | | PHYSICAL DAMAGE AND EXPOSED TO THE WEATHER. NEC 358.12 | | | | E301 | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | E601 | | PANEL EQH2 DOES NOT MATCH WITH THE RISER PLAN ON E002. | | NEC 215.5 | | PANEL NH1A DOES NOT MATCH WITH THE RISER PLAN ON E003. | | | | NOTE: | | SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, FIRE | | ALARM SYSTEMS AND LIGHTNING PROTECTION. | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|