Plan Review Notes
Plan Review Notes For Permit 12100269
Permit Number 12100269
Review Stop E
Sequence Number 1
Notes
Date Text
2012-11-06 11:15:0412100269
 4847 FRED GLADSTONE DRIVE
 RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 E003
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 E005:
 ELECTRICAL METALLIC TUBING (EMT) IS NOT AN ACCEPTABLE
 WIRING METHOD AS SHOWN MOUNTED ON THE ROOF EXPOSED TO
 PHYSICAL DAMAGE AND EXPOSED TO THE WEATHER. NEC 358.12
  
 E301
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 E601
 PANEL EQH2 DOES NOT MATCH WITH THE RISER PLAN ON E002.
 NEC 215.5
 PANEL NH1A DOES NOT MATCH WITH THE RISER PLAN ON E003.
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, FIRE
 ALARM SYSTEMS AND LIGHTNING PROTECTION.
  