2013-01-18 09:20:31BUILDING PLAN REVIEW
 PERMIT: 12100245
 ADD: 5200 EAST AVE.
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1300
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 JAN. 18/ 2013
 ACTION: DENIED
  
 1A) 2ND REQUEST. SHEET C2 & A-101 BOTH INDICATE THE
 EXISTING FINISH FLOOR ELEVATION AS 16.34' NAVD 88. THIS
 BUILDING IS LOCATED IN A AH FLOOD ZONE WITH A BASE
 FLOOD ELEVATION AT 17.00' NGVD. THE FLOOD INSURANCE
 RATE MAP (FIRM) IS USING TTHE NGVD 29 TERMINOLOGY AND
 ALL ELEVATIONS SHALL BE NGVD ON THE PLANS AS WELL AS
 FLOOD ELEVATION CERTIFICATES. PLEASE PROVIDE THE
 EXISTING SLAB ELEVATION FOR THIS STRUCTURE IN NGVD.
 PLEASE NOTE A ELEVATION OF 17.5 FT. NGVD IS REQUIRED BY
 CITY MUNI CODE 94-546 FOR RESIDENTIAL CONSTRUCTION. FOR
 COMMERCIAL PROJECTS THEY CAN BE FLOOD PROOFED PLEASE
 SEE CITY MUNI-CODE 94-546(2) .
  
 IF THE DESIGNER OF RECORD IS GOING TO USE THE NGVD
 TERMINOLOGY THEY WILL ALSO NEED TO PROVIDE THE
 EQUIVALENCY ON THE PLANS IN NGVD 29 TERMINOLOGY. THE
 ADOPTED FLOOD MAPS ARE IN NGVD AND WHEN FEMA COMPLETES
 OUR YEARLY AUDIT THEY WILL NOT ACCEPT THE FLOOD ZONE
 CERTIFICATES UNLESS THEY ARE IN NGVD.
  
 PLEASE NOTE THE ELEVATION CERTIFICATE SUBMITTED IS A
 COPY, NOT AND ORIGINAL SIGNATURE, NOT SEALED, PLEASE
 NOTE UNDER THE HEADING A4 BUILDING USE: TEMORARY
 KITCHEN, AND UNDER THE HEADING A5 NAD 1983 AND HEADING
 B9 BASE FLOOD 15.45'. HEADING C2 VERTICAL DATUM NAVD
 1988.
 SECTION D COMMENTS: ITEM B9. BFE NAVD 1998/ BFE= 17.00'
 NGVD 1929
  
 PLEASE SEE THE ORIGINAL COMMENT THE CITY MUNI CODE
 REQUIRES AN ADDITIONAL 0.5 FT IN ELEVATION OR A MINIMUM
 HEIGTH OF 17.5 FT NGVD FOR A FINISH FLOOR ELEVATION FOR
 THE ADDITION. I AM TAKING THE CERTIFICATE THAT THE
 EXISTING DINING ROOM IS AT THIS BASE FLOOD ELEVATION OR
 0.5" BELOW THE ESTABLISHED FLOOD ELEVATION OF 17.5'
 NGVD. THERE IS TWO
 AVENUES THAT NEED TO BE DECIDED WHICH WILL BE BETTER
 FOR YOUR CLIENT, SINCE THIS IS A COMMERCIAL PROJECT THE
 CITY MUNI-CODE DOES ALLOW FOR FLOOD PROOFING WHEN THE
 FINISHED FLOOR IS LOWER THAN THE REQUIRED ELEVATION IF
 TRAVELING IN THAT DECISSION THE FLOOD PROOFING HAS TO
 BE ONE FOOT HIFHER THAN THE 17.5' NGVD THE OTHER OPTION
 WITH SUBSTANIAL IMPROVEMENTS AN ADDITION PLUS OTHER
 WORK TO THE STRUCTURE WOULD BE TO RAISE THE EXISTING
 FLOOR TO THE REQUIRED 17.5 FT NGVD AND THE NEW ADDITION
 TO BE POURED AND FINISHED AT THE 17.5 NGVD. AN
 EVALUATION IS TO BE PREPARED TO DETERMINE IF ALL THE
 PROPOSED WORK WILL TRIGGER THE SUBSTANIAL IMPROVEMENT
 REQUIREMENT.
  
 1B) THIS SITE HAS MULTIPLE BUILDINGS UNDER ONE PCN
 NUMBER WITHOUT IDENTIFYING BUILDINGS IN REGARDS TO
 PERMITTING. PLEASE REVIEW CITY MUNI-CODE IN REGARDS TO
 SUBSTANIAL IMPROVEMENTS AND THE REQUIREMENTS FOR ALL
 NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS SHALL BE
 ANCHORED TO PREVENT FLOTATION, COLLAPSE OR LATERAL
 MOVEMENT OF THE STRUCTURE, AND SHALL BE CONSTRUCTED
 WITH MATERIALS AND UTILITY EQUIPMENT RESISTANT TO FLOOD
 DAMAGE BY METHODS AND PRACTICES THAT MINIMIZE FLOOD
 DAMAGE.
  
 IT WILL BE DIFFICULT TO DETERMINE SUBSTANIAL
 IMPROVEMENT SINCE THE BUILDINGS ON THIS SITE DO NOT
 HAVE DIFFERENT ADDRESSES.
  
 2) 1/03/2013 COMPLIED.
  
 3) SEMI-COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. PACKET HAS VARIOUS TYPES OF
 GLAZING WITH DIFFERENT PRESSURES, MULLIONS ALSO
 DIFFERNT PRESSURES THEY ARE NOT IDENTIFIED (CIRCLE)
 (B) WINDOWS PACKET HAS VARIOUS TYPES OF GLAZING WITH
 DIFFERENT PRESSURES, MULLIONS ALSO DIFFERNT PRESSURES
 THEY ARE NOT IDENTIFIED (CIRCLE)
 (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS PACKET HAS
 VARIOUS TYPES OF GLAZING WITH DIFFERENT PRESSURES,
 MULLIONS ALSO DIFFERNT PRESSURES THEY ARE NOT
 IDENTIFIED (CIRCLE)
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFING
 INSULATION. SUB-SYSTEM TYPE A(2) PAGE 10 OF 27 TABBED
 WITH A MAXIMUM DESIGN PRESSURE OF -45 PSF/ LIMITATION
 #7 REQUIRING ENHANCED FASTENING IN ZONES 2 & 3 BY A
 DESIGN PROFESSIONAL.
  
 (G) PRE-ENGINEERED A/C STANDS, A/C CURBING, ROOF TOP
 FANS THERE MAY BE A PROBLEM IF THE ALUMINUM ROOF TOP
 FANS ARE USED, LOW PRESSURES
  
 NEW COMMENT: PLEASE REVIEW: 2010 FBC-B 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
 THE LATERAL FORCE ON ROOFTOP STRUCTURES AND EQUIPMENT
 WITH AF LESS THAN (0.1BH) LOCATED ON BUILDINGS OF ALL
 HEIGHTS SHALL BE DETERMINED FROM EQUATION 29.5-1 OF
 ASCE 7 IN WHICH THE VALUE OF GCF SHALL BE TAKEN AS 3.1.
 GCF SHALL BE PERMITTED TO BE REDUCED LINEARLY FROM 3.1
 TO 1.1 AS THE VALUE OF AF IS INCREASED FROM (0.1BH) TO
 (BH). THE VALUE OF G FROM SECTION 26.9 OF ASCE 7 SHALL
 NOT BE USED. ADDITIONALLY, A SIMULTANEOUS UPLIFT FORCE
 SHALL BE APPLIED, GIVEN BY EQUATION 29.5-1 OF ASCE 7 IN
 WHICH GCF = 1.5 AND AF IS REPLACED BY THE HORIZONTAL
 PROJECTED AREA, AR, OF THE ROOFTOP STRUCTURE OR
 EQUIPMENT. FOR THE UPLIFT FORCE GCF SHALL BE PERMITTED
 TO BE REDUCED LINEARLY FROM 1.5 TO 1.0 AS THE VALUE OF
 AR IS INCREASED FROM (0.1BL) TO (BL).
  
  
 5) 2ND REQUEST. 2010 ENERGY CODE 402.3 FENESTRATION
 402.3.2 PLEASE PROVIDE SHGC FOR WINDOWS. THE RESPONSE
 INDICATED THE SOLAR HEAT GAIN TO BE 0.65. AND REFER TO
 INCLUDED SUPPLEMENTAL DOCUMENTS, ONLY GLAZING PRODUCT
 APPROVAL WERE SUBMITTED FOR WIND PRESSURE AND LARGE
 MISSILE TESTING.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PROVISO: FOUNTAIN TO BE SUBMITTED UNDER SEPERATE
 PERMIT APPLICATION, PULL FEES FOR SEPERATE REVIEW AND
 INSPECTIONS.
  
 10) PROVISO: AWNINGS DEPICTED IN PLANS ALSO REQUIRE A
 SEPERATE PERMIT, PULL FEES FOR SEPERATE PERMIT, REVIEW
 AND INSPECTIONS.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) FAILURE FOR THE CONTRACTOR TO PUT IN THE NEW SHEETS
 AND REMOVE THE OLD SHEETS. INFORMATIONAL: WHEN
 RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved