2012-10-15 09:20:18 | FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEET P-2.1 - P4.1 PLEASE ATTACH THE MOP SINKS TO |
| THE GREASE LINE. |
| 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES REQUIRED. |
| A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| PREPARATION AREAS |
| |
| 2. SHEET P-2.1 & P4.1 - PLEASE ADD A VENT TO THE WATER |
| CLOSET IT IS NOT SHOWN AS BEING VENTED . |
| 901.2.1 VENTING REQUIRED. |
| EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| THIS CHAPTER. |
| 909.1 HORIZONTAL WET VENT PERMITTED. |
| ...ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL |
| CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| HORIZONTAL WET VENT. |
| |
| 3. P2.1 & P4.1 THE DISHWASHER IS NOT REQUIRED TO |
| CONNECT TO THE GREASE LINE DUE TO THE PRE-RINSE. |
| 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES REQUIRED. |
| A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL |
| KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY |
| CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL |
| INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR |
| SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS |
| INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| UNITS AND <<< |
| SINKS.>>>>GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES |
| AND EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE |
| DISCHARGED. |
| |
| 4. P1107.3P6.1 SCUPPERS SHALL NOT HAVE AN OPENING |
| DIMENSION OF LESS THAN 4 INCHES (102 MM). |
| PLEASE CORRECT THE NOTE 6" X 3" |
| |
| NOTE: |
| FUEL GAS, GREASE TRAP AND IRRIGATION ARE NOT INCLUDED |
| IN THIS REVIEW. SEPARATE APPLICATIONS, PLANS, REVIEWS, |
| FEES, AND PERMITS REQUIRED. |
| |