2012-10-19 10:18:295200 EAST AVENUE
 PERMIT #12100245
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
  
 FIRE ALARM SYSTEM
 FIRE ALARM SYSTEM SHALL MONITOR FIRE SPRINKLER SYSTEM
 FLOW AND TAMPER SWITCHES. COORDINATE LOCATION OF THE
 DEVICES TO BE MONITORED.
  
  
 FIRE SPRINKLER SYSTEM
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 FIRE SPRINKLER AREA OF OPERATION SHALL BE INCREASED BY
 30% WHEN THE CEILING/ROOF PITCH EXCEEDS 2 IN 12.
  
 PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A
 BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING
 AS THE HEIGHT OF THE WALL FACING THE BACKFLOW
 PREVENTER.
  
 INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S)
 AND THE PROPOSED LOCATION OF THE FIRE DEPARTMENT
 CONNECTION. FDC SHALL BE LOCATED WITHIN 150 FEET OF A
 HYDRANT AND BE READILY ACCESSIBLE TO THE FIRE
 DEPARTMENT.
  
 PROVIDE FIRE HYDRANT FLOW TEST DATA.
  
  
 KITCHEN
 THE MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  