Plan Review Notes
Plan Review Notes For Permit 12100129
Permit Number 12100129
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-10-09 11:13:182047 PALM BEACH LAKES BOULEVARD
 PERMIT #12100129
 MASTER #12030309
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NONE OF THE ROOM HEAT OR SMOKE DETECTORS ARE SHOWN FROM
 THE ENGINEERING CONSTRUCTION DOCUMENTS (SHEET E6).
  
 NO SUPERVISION IS PROVIDED FOR THE AUTOMATIC SPRINKLER
 SYSTEM OR BACKFLOW PREVENTER. COORDINATE LOCATIONS OF
 TAMPER AND FLOW SWITCHES.
  
 PROVIDE A MANUAL PULL STATION AT THE NURSE CONTROL
 STATION.
  
 NO NOTIFICATION APPLIANCES PROVIDED IN PATIENT TOILET
 #109, STAFF LOCKER #128, AND CORRIDOR #125 (OUTSIDE OF
 OPERATING ROOM #119).
  
 NO NOTIFICATION APPLIANCES LOCATED IN THE OPERATING
 ROOMS. INDICATE THE METHOD FOR ALERTING THE OCCUPANTS
 OF A FIRE ALARM CONDITION.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  