 PLEASE PROVIDE A RESPONSE TO THE FOLLOWING ELECTRICAL
 REVIEW COMMENTS.
  
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.70
  
  