2012-11-02 16:14:44 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 101.4.3 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 2- BEDROOM #1: FRONT WINDOW IS GOING TO BE ENCLOSED. |
| SPECIFY SIZE OF EXISTING WINDOW TO BE ENCLOSED. EGRESS |
| CAN'T BE REDUCED. SEC. 601.2 OF 2010 FBC-EXISTING |
| BUILDING. PROVIDE WINDOW MANUFACTURER CUT SHEETS FOR |
| OTHER WINDOW ON THIS BEDROOM TO DEMONSTRATE THAT THIS |
| WINDOW WILL MEET THE EGRESS REQUIREMENTS OF SEC. R310 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| 3- SHEET 1.2: |
| A) DESIGN PARAMETERS: (1) REVISE THE ROOF LIVE LOAD. |
| SEE TABLE R301.6 OF 2010 FBC-RESIDENTIAL AND REVISE AS |
| REQUIRED. (2) ALSO REVISE THE ROOF LIVE LOAD SHOWN ON |
| STRUCTURAL NOTE #2(A). |
| |
| B) REVISE STRUCTURAL NOTE #2(C). DESIGN PARAMETERS |
| SPECIFY EXPOSURE "D" NOT "B". REVISE AS REQUIRED TO |
| MATCH. |
| |
| C) SPECIFY SAFETY GLASS AS REQUIRED BY SEC. R308.4 FOR |
| EAST WINDOWS ON BOTH BEDROOMS. AND, FOR BATHROOM |
| WINDOW. THIS APPLIES IF WINDOWS DON'T HAVE IMPACT |
| GLASS. PRODUCT APPROVAL WAS NOT SUBMITTED. |
| |
| D) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE LANDING |
| AS REQUIRED BY SEC. R311.3. (2) PROVIDE HANDRAILS AS |
| REQUIRED BY SEC. R311.7.7. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ALL WINDOWS AS SHOWN ON PLANS. |
| |
| B) ALL EXTERIOR DOORS AS SHOWN ON PLANS. |
| |
| C) ALL WINDOW MULLIONS AS SHOWN ON PLANS. |
| |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND |
| PAGE SHOWING THE CONNECTOR. |
| |
| E) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. |
| |
| 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. UPDATE |
| VALUATIONS AS REQUIRED. VA;LUATION TO INCLUDE ALL |
| PROFESSIONAL DESIGN FEES, ALL LABOR AND MATERIALS AND |
| CONTRACTOR'S OVERHEAD AND PROFIT. PROVIDE COPY OF |
| SIGNED CONTRACT SIGNED BY OWNER AND CONTRACTOR. |
| |
| 7- SHEET 2.2: |
| A) DESIGN PRESSURES FOR DOORS AND WINDOWS DON'T |
| CORRESPOND TO EXPOSURE "D' AS SPECIFIED ON THE DESIGN |
| CRITERIA ON SHEET 1.2. REVISE AS REQUIRED. SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| |
| B) TYPICAL WOOD FRAME DETAILS FOR WINDOWS, DOORS AND |
| WALLS: (1) SPECIFY SIZE OF HEADERS. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. (2) BELOW THE WINDOW OPENINGS THERE |
| IS A NOTE SAYING THAT NO CONNECTORS ARE REQUIRED. |
| CLARIFY WHY NOT. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 8- PROVIDE COMPLETE WALL SECTION SHOWING ALL FRAMING |
| MEMBERS, CONNECTORS, INSULATION, WALL SHEATHING, DOUBLE |
| VAPOR BARRIER, STUCCO THICKNESS, ETC. AS REQUIRED BY |
| SEC. 107.3.5.3(5) CITY AMENDMENTS TO FBC. |
| |