2012-11-27 09:59:56 | BUILDING PLAN REVIEW |
| PERMIT: 12100015 |
| ADD: 2316 S DIXIE HWY |
| CONT: ARCA CONSTRUCTION |
| TEL: (772)336-4296 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| PROVISO: |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| 4A) 11/21/2012 I SPOKE WITH THE DESIGNER OF RECORD A |
| CORRECTED WIND DESIGN CRITERIA WILL NEED TO BE |
| SUBMITTED , PLEASE CALCULATE TO AT LEAST THE MINIMUM |
| FOR OUR WIND SPEED ZONE OF 170 MPH VULT. |
| 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE |
| TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE |
| HAND WRITTEN IN, IT CAN BE TAKEN THIS IS A GENERIC |
| LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE |
| LETTER HEADING. |
| 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER |
| OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING |
| INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE |
| DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| THE ENGINEER OF RECORD FOR REVIEW. |
| |
| |
| 6) COMPLIED. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |