2012-10-10 16:38:22 | BUILDING PLAN REVIEW |
| PERMIT: 12100015 |
| ADD: 2316 S DIXIE HWY |
| CONT: ARCA CONSTRUCTION |
| TEL: (772)336-4296 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| OCT. 10/ 2012 |
| ACTION: DENIED |
| |
| 1) SHEET P-2 THE MODIFIED WINDOW DETAIL INDICATES THE |
| USE OF A SIMPSON ABU66 POST BASEFOR USE WITH THE BUILT |
| UP POST/ COLUMN. PLEASE PROVIDE FLORIDA PRODUCT |
| APPROVAL FOR SIMPSON ABU66 AND PROVIDE TYPE OF ANCHORS |
| TO BE INSTALLED IN THE SLAB AND BEAM ABOVE. PROVIDE |
| QUANITY OF ANCHORS, DIAMETER AND LENGTH OF ANCHOR TYPE. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: 9N-3 |
| (31)(G) STRUCTURAL COMPONENTS. |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS, ... |
| |
| 3) P-2 INDICATES THE REMOVAL OF WINDOW, THE MULLION |
| WILL STILL BE PART OF THE COMPONENTS AND CLADDING HOW |
| WILL THE MULLION AND NEW POST/ COLUMN BE COMBINED, OLD |
| MULLIONS DID NOT TRANSFER LOADS WITH TOP AND BOTTOM |
| ANGLE PLATES? ADDITIONAL INFORMATION REQUIRED |
| 107.2.1.3. |
| |
| 4)PROVISO: P-2 INDICATES THE KIOSK ENGINEERING BY |
| OTHERS, PLEASE PROVIDE ENGINEERING BEFORE FRAMING |
| INSPECTION. THE KIOSK IS PART OF COMPEONENTS & CLADDING |
| AND WILL REQUIRE ENGINEERING FOR 170 MPH 3ECOND GUST V |
| ULTIMATE. 2010 FBC-B 1609.4.4.1. |
| |
| 5) SHEET C-1 AND P-1 DOESN'T SPECIFY IF THIS BUILDING |
| HOUSES 1 TENANT OR TWO TENANTS IF TWO TENANTS THEN 2010 |
| FBC-B 709.1.6 APPLIES NEEDING 1 HOUR SEPERATION. |
| |
| 6) THE OTHER ISSUE C-1 & P-1 DOESN'T INDICATE THIS TO |
| BE A MIXED USE OCCUPANCY , PLEASE NOTE TABLE 508.4 DOES |
| NOT REQUIRE RATING BETWEEN THE TWO OCCUPANCIES. |
| |