Plan Review Notes
Plan Review Notes For Permit 12100013
Permit Number 12100013
Review Stop P
Sequence Number 1
Notes
Date Text
2012-11-05 08:50:232010 FBC
 PLUMBING DENIED
  
 1) THE PLUMBING RISER DIAGRAM ON SHEET A-4 SHOWS TWO
 WASHING MACHINE BRANCH DRAINS & VENTS AND THE PLANS
 INDICATE ONE CLOTHES WASHER. CITY AMENDMENTS 107.2.1
 PLEASE CORRECT.
  
 2) THE PLUMBING RISER DIAGRAM DOES NOT SHOW THE BRANCH
 DRAIN & VENT FOR THE KITCHEN SINK THAT IS SPECIFIED ON
 THE PLANS. CITY AMENDMENTS 107.2.1 PLEASE CORRECT.
  
 3) THE DRAIN TRAP AND TRAP ARM FOR THE WASHING MACHINE
 IS REQUIRED TO BE 2" PER FBCR P3201.7 AND THE RISER
 DIAGRAM HAS 1-1/2". PLEASE CORRECT.
  
 4) CITY AMENDMENTS 107.2.1 REQUIRES ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA TO BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. PLEASE CORRECT.
  