Plan Review Notes For Permit 12100013 |
Permit Number |
12100013 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-05 14:26:48 | 2010 FBC & 2008 NEC | | | | ELECTRIC DENIED | | | | 1) SEE BUILDING REVIEW FOR SMOKE ALARM AND CARBON | | MONOXIDE ALARM COMMENTS. FBCR 314 AND 315 | | | | 2) SHOW COMPLIANCE WITH 2008 NEC ARTICLE 406.11 FOR | | TAMPER-RESISTANCE RECEPTACLES. | | | | 3) SHOW COMPLIANCE WITH ART. 210.12 FOR ARC-FAULT | | CIRCUIT-INTERRUPTER (AFCI) REQUIREMENTS. | | | | 4) SHOW COMPLIANCE WITH ART.210.52 (E) (1) FOR THE | | REQUIRED OUTDOOR (GFCI) RECEPTACLE AT THE FRONT OF THE | | DWELLING. | | | | 5) A RECEPTACLE IS REQUIRED IN BEDROOM #5, BETWEEN THE | | DOOR TO THE ROOM AND THE CLOSET DOOR PER ART. 510.52 | | (A) (2). | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|