Plan Review Notes
Plan Review Notes For Permit 12090745
Permit Number 12090745
Review Stop P
Sequence Number 1
Notes
Date Text
2012-10-17 12:39:27FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. NO PLUMBING DRAWINGS WERE INCLUDED WITH THIS SET OF
 PLANS.
  
 2. DEPENDING UPON THE OCCUPANCY TYPE AND NUMBER OF
 OCCUPANTS, DRINKING FOUNTAINS MAY BE REQUIRED
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 FBC 107.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. ROOF DRAINAGE
 8. BACK FLOW PREVENTION
 13. PLUMBING RISER
  
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  