Plan Review Notes For Permit 12090745 |
Permit Number |
12090745 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-10-17 12:39:27 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. NO PLUMBING DRAWINGS WERE INCLUDED WITH THIS SET OF | | PLANS. | | | | 2. DEPENDING UPON THE OCCUPANCY TYPE AND NUMBER OF | | OCCUPANTS, DRINKING FOUNTAINS MAY BE REQUIRED | | PLUMBING TABLE 403.1 (E) (F) | | FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | 602.7. | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | FOUNTAINS. | | | | FBC 107.3.5.1.3 PLUMBING MINIMUM PLAN REVIEW CRITERIA | | FOR BUILDINGS. | | 1. MINIMUM PLUMBING FACILITIES | | 2. FIXTURE REQUIREMENTS | | 3. WATER SUPPLY PIPING | | 4. SANITARY DRAINAGE | | 5. WATER HEATERS | | 6. VENTS | | 7. ROOF DRAINAGE | | 8. BACK FLOW PREVENTION | | 13. PLUMBING RISER | | | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|