Plan Review Notes
Plan Review Notes For Permit 12090709
Permit Number 12090709
Review Stop B
Sequence Number 1
Notes
Date Text
2012-09-27 12:24:37BUILDING PLAN REVIEW
 PERMIT: 12090709
 ADD: 1483 N MANGONIA CIR
 CONT: LLOYD'S ROOFING
 TEL: (561)312-0803
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 PROVISO:
 1507.2.5 ASPHALT SHINGLES.
  
 1507.2.8 UNDERLAYMENT APPLICATION.
  
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE) AND UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE),
 UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN THE
 FOLLOWING MANNER. APPLY A MINIMUM 19-INCH-WIDE (483 MM)
 STRIP OF UNDERLAYMENT FELT PARALLEL WITH AND STARTING
 AT THE EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE.
 STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM)
 SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19
 INCHES (483 MM), BY FASTENED SUFFICIENTLY TO HOLD IN
 PLACE. DISTORTIONS IN THE UNDERLAYMENT SHALL NOT
 INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL. FOR
 ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE) OR GREATER, UNDERLAYMENT
 SHALL BE ONE LAYER APPLIED IN THE FOLLOWING MANNER.
 UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, PARALLEL
 TO AND STARTING FROM THE EAVE AND LAPPED 2 INCHES (51
 MM), FASTENED SUFFICIENTLY TO HOLD IN PLACE.
 DISTORTIONS IN THE UNDERLAYMENT SHALL NOT INTERFERE
 WITH THE ABILITY OF THE SHINGLES TO SEAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]