Plan Review Notes For Permit 12090615 |
Permit Number |
12090615 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-11-17 15:53:01 | 2716 OKEECHOBEE BLVD | | PERMIT # 12040166 | | TRACKING #12090615 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FLORIDA BUILDING CODE SECTION 105.3.1.2 REQUIRES THE | | PLANS TO BE DESIGNED AND SIGNED/SEALED BY A | | PROFESSIONAL ENGINEER, NOT AN ARCHITECT (REFERENCE | | FLORIDA STATUTE 471). | | | | REPEAT COMMENT: FIRE ALARM PLANS SHALL BE SIGNED AND | | SEALED BY A PROFESSIONAL ENGINEER WHEN THE JOB VALUE | | EXCEEDS $5,000. | | | | BATTERY CALCULATIONS NOT SUBMITTED FOR ANY NAC | | CIRCUITS. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|