Plan Review Notes For Permit 12090615 |
Permit Number |
12090615 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-10-02 12:30:23 | 2716 OKEECHOBEE BLVD | | PERMIT # 12040166 | | TRACKING #12090615 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FIRE ALARM PLANS SHALL BE SIGNED AND SEALED BY A | | PROFESSIONAL ENGINEER WHEN THE JOB VALUE EXCEEDS | | $5,000. | | | | THE REVISION CLOUDS DO NOT MATCH THE INCREASED SCOPE OF | | WORK. | | | | VOLTAGE DROP AND BATTERY CALCULATIONS NOT SUBMITTED. | | | | PLANS DO NOT INDICATE ROOM NAMES/NUMBERS, CEILING | | HEIGHTS ETC. | | | | SPACING AND LOCATION OF FIRE ALARM NOTIFICATION | | APPLIANCES LEAVE SEVERAL AREAS WITH INSUFFICIENT | | NOTIFCATION. FOR EXAMPLE THE SOUTHWEST ROOM HAS ONLY | | ONE APPLIANCE AND IS LOCATED A GREAT DISTANCE FROM THE | | EAST WALL. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|