Plan Review Notes For Permit 12090544 |
Permit Number |
12090544 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-10-03 10:17:25 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE EQUIPMENT SIZING CALCULATIONS SPECIFY 28,841 | | TOTAL BTUH AND 2.4 COOLING TONS, WHICH REQUIRES A 2.5 | | TON A/C UNIT. THE ENERGY CALCULATION FORM THAT WAS | | SUBMITTED PREVIOUSLY ALSO LISTS A 30,000 BTUH (2.5 TON) | | UNIT, IN ADDITION TO A 36,000 BTUH (3 TON) UNIT AND A | | 60,000 BTUH (5 TON) UNIT. HOWEVER, THE EQUIPMENT | | SCHEDULE ON THE PLANS LISTS TWO 3 TON AND ONE 5 TON | | UNITS. PLEASE CORRECT. FBCR M1401.3 & FBC ENERGY | | CONSERVATION SECTION 405 | | | | 2) THE PREVIOUSLY SUBMITTED ENERGY CALCULATION FORM | | SPECIFIES ALL THREE UNITS AS 16 SEER. THE EQUIPMENT | | SCHEDULE ON THE PLANS LISTS THE 5 TON AS 15 SEER PLEASE | | CORRECT. FBCR M1401.3 & FBC ENERGY CONSERVATION SECTION | | 405 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|