2012-10-11 13:45:32 | 2275 PALM BEACH LAKES BOULEVARD |
| PERMIT #12090498 |
| MASTER #12030334 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SPRINKLER PLANS |
| REPEAT COMMENT: THE SPRINKLER PLANS AND HYDRAULIC |
| CALCULATIONS ARE NOT SIGNED AND SEALED BY THE |
| PROFESSIONAL ENGINEER (B. MASKOL). |
| NEW COMMENT: NO FIRE PROTECTION ENGINEERING DOCUMENTS |
| WERE EVER SUBMITTED WITH THE MASTER PERMIT (#12030334); |
| THEREFORE, THE SHOP DRAWINGS NEED TO BE SIGNED/SEALED |
| OR ENGINEERING DOCUMENTS NEED TO BE SIGNED/SEALED AND |
| SUBMITTED WITH THE ISSUED MASTER PERMIT. |
| |
| REPEAT COMMENT: PLEASE PROVIDE HYDRAULIC CALCULATIONS |
| FOR THE SOUTHWEST (CLASSROOM AREA) OF THE BUILDING |
| (ROOM #105A & #105B). |
| NEW COMMENT: PLEASE INCLUDE THE NODES ON THE FLOOR |
| PLAN. THE HYDRAULIC AREA (ROOM #105A & #105B) IS FOR |
| INDICATING LOCATION ONLY, THE REMOTE AREA STILL NEEDS |
| TO BE AT LEAST 900 SQ.FT. (DEPENDENT UPON CEILING |
| HEIGHT) AND HAVE A LENGTH OF 1.2 X SQUARE ROOT OF THE |
| REMOTE AREA. |
| |
| |
| NOTE:THE FOLLOWING CIVIL PLAN REVIEW COMMENTS ARE FOR |
| INFORMATIONAL PURPOSES ONLY. A SPRINKLER PERMIT FOR THE |
| INTERIOR WORK CAN BE ISSUED AS THE UNDERGROUND PIPING |
| WILL REQUIRE A SEPARATE PERMIT. |
| |
| METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF |
| WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A |
| SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE |
| UNDERGROUND FIRE SERVICE MAIN. |
| |
| A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE |
| DEPARTMENT CONNECTION. |
| |
| **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF |
| 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE PER |
| SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE |
| CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES. |
| |
| PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR |
| SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| POSITION. |
| |
| PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| DEPARTMENT CONNECTION. |
| |