2012-10-11 13:45:322275 PALM BEACH LAKES BOULEVARD
 PERMIT #12090498
 MASTER #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPRINKLER PLANS
 REPEAT COMMENT: THE SPRINKLER PLANS AND HYDRAULIC
 CALCULATIONS ARE NOT SIGNED AND SEALED BY THE
 PROFESSIONAL ENGINEER (B. MASKOL).
 NEW COMMENT: NO FIRE PROTECTION ENGINEERING DOCUMENTS
 WERE EVER SUBMITTED WITH THE MASTER PERMIT (#12030334);
 THEREFORE, THE SHOP DRAWINGS NEED TO BE SIGNED/SEALED
 OR ENGINEERING DOCUMENTS NEED TO BE SIGNED/SEALED AND
 SUBMITTED WITH THE ISSUED MASTER PERMIT.
  
 REPEAT COMMENT: PLEASE PROVIDE HYDRAULIC CALCULATIONS
 FOR THE SOUTHWEST (CLASSROOM AREA) OF THE BUILDING
 (ROOM #105A & #105B).
 NEW COMMENT: PLEASE INCLUDE THE NODES ON THE FLOOR
 PLAN. THE HYDRAULIC AREA (ROOM #105A & #105B) IS FOR
 INDICATING LOCATION ONLY, THE REMOTE AREA STILL NEEDS
 TO BE AT LEAST 900 SQ.FT. (DEPENDENT UPON CEILING
 HEIGHT) AND HAVE A LENGTH OF 1.2 X SQUARE ROOT OF THE
 REMOTE AREA.
  
  
 NOTE:THE FOLLOWING CIVIL PLAN REVIEW COMMENTS ARE FOR
 INFORMATIONAL PURPOSES ONLY. A SPRINKLER PERMIT FOR THE
 INTERIOR WORK CAN BE ISSUED AS THE UNDERGROUND PIPING
 WILL REQUIRE A SEPARATE PERMIT.
  
 METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF
 WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A
 SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE
 UNDERGROUND FIRE SERVICE MAIN.
  
 A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE
 DEPARTMENT CONNECTION.
  
 **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE
 CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730